83.2V 233.1Ah ENERGY STORAGE STATION BATTERY | ATOMFAIRCOMMERCIAL GRADE · PRODUCTION
|
|||||||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||
|
TAILORED SOLUTIONS FOR RESEARCH
Contact our engineering team for technical support or official institutional quotations.
EMAIL: inquiry@atomfair.com
|
|||||||||||||||||||||||||||||||||
|
Manufacturer: Atomfair LLC
Brand: ATOMFAIR®
|
This battery module requires strict adherence to charge and discharge temperature windows to prevent thermal runaway or capacity degradation. Storage must remain within -30°C to 60°C with unlimited humidity tolerance, and operation is limited to altitudes below 2000 meters.
- Charge Temperature Constraint: Charging is permitted only within 0°C to 50°C to avoid lithium plating and internal damage.
- Discharge Temperature Constraint: Discharging is permitted only within -20°C to 50°C to maintain safe electrochemical stability.
- Current Rating Constraint: Peak charge current must not exceed 233 A (1C) and peak discharge current must not exceed 466 A (2C) to prevent overcurrent stress.
- Altitude Constraint: Operation is restricted to altitudes at or below 2000 meters to ensure adequate cooling and insulation integrity.
This procedure covers initial inspection, electrical connection, and operational verification for the high-voltage battery module. Follow all steps sequentially to ensure safe integration into an EV fast charging or grid storage system.
Required Equipment: Insulated torque wrench, Digital multimeter rated for DC 100V, Personal protective equipment (PPE) including voltage-rated gloves
- Inspect the chassis and terminals
Inspect the chassis for physical damage and verify terminal cleanliness before any electrical connection. - Measure open-circuit voltage
Measure the open-circuit voltage across the main terminals using a digital multimeter to confirm it is within the 65.0 V to 94.9 V working range. - Connect to the DC bus
Connect the positive and negative terminals to the DC bus using appropriately rated cables, ensuring torque specifications are met with an insulated torque wrench. - Verify ambient temperature
Verify that the ambient temperature is between 0°C and 50°C before initiating the first charge cycle. - Initiate a controlled charge
Initiate a controlled charge at or below 116 A continuous rated current, monitoring voltage rise to ensure it does not exceed 94.9 V. - Confirm system communication
Confirm that the battery management system communicates correctly with the charging controller before full-power operation.
What are the continuous and peak discharge current ratings of the 83.2V 233.1Ah energy storage battery?
The battery has a continuous rated discharge current of 233 A (1C) and a peak burst discharge current of 466 A (2C). These ratings are specified in the product documentation to support rapid energy transfer for EV fast charging infrastructure.
What is the working voltage range and how does it affect compatibility with existing DC bus systems?
The working voltage range is 65.0 V DC to 94.9 V DC, with a nominal voltage of 83.2 V DC. This allows the battery to integrate with 83.2V nominal DC bus systems common in grid energy storage and EV charging stations, provided the bus voltage stays within the specified limits.
What are the storage and operating temperature limits to ensure safe long-term use?
The battery can be stored at -30°C to 60°C with unlimited humidity protection, and operates during charging from 0°C to 50°C and during discharging from -20°C to 50°C. These wide ranges enable reliable deployment in diverse climates, but users must avoid exceeding these thresholds to prevent damage.
This 83.2V 233.1Ah energy storage battery delivers 19.39kWh with 1C charge/2C discharge peak rates, suited for high-throughput EV charging and grid buffer applications, but requires careful handling due to its 100 kg mass and altitude restrictions.
Positive
- High power charge/discharge capability: Rated charge 116A (peak 233A at 1C) and rated discharge 233A (peak 466A at 2C) enable rapid energy transfer for EV fast charging infrastructure.
- Wide environmental operating range: Operates from -20°C to 50°C discharge, 0°C to 50°C charge, and stores from -30°C to 60°C with unlimited humidity tolerance, ensuring reliability in diverse climates.
Trade-offs
- Heavy chassis weight: The 100 ± 5 kg standalone module requires robust mechanical support and specialized handling equipment for installation and maintenance.
- Altitude operational limit: Maximum operating altitude of ≤2000 meters restricts deployment in high-altitude regions without derating or additional engineering assessment.
Every advanced material, component, equipment, and instrument in our catalog is backed by rigorous testing. We maintain strict internal quality management frameworks and align with CE conformity metrics to deliver transparent, reproducible performance data via our public open-science repository.
To request raw batch performance data, submit formal vendor registration paperwork, or execute a fast-turnaround R&D manufacturing loop, contact us at inquiry@atomfair.com.
Item is dispatched under the Atomfair Shipping & Delivery Framework (Free worldwide shipping on orders over $59 USD excl. heavy equipment). Return is governed by the Atomfair Return & Refund Policy (7-day technical return window).